
But when one of them actually does shut the system down, you
have a troubleshooting problem: Which one of them did it? You
cannot determine the cause of shutdown by examining the switches,
because they tend to dance around after shutdown.
For example, if the nozzle gets too hot, the "hot nozzle"
switch opens, shutting down the conveyor motor and water supply
valve. The conveyor belt then coasts to a stop and the "belt
stopped" switch opens. The "low pressure" switch also opens
because the water supply valve is shut off. And in a few minutes
the "hot nozzle" switch re-closes because the nozzle has cooled
down.
By the time a technician arrives, the original cause of the
shutdown has disappeared. The current positions of the interlock
switches are immaterial. The only thing the tech can do is
restart the process and wait a few minutes. If nothing happens
(often the case), he moves on to tilt at other windmills.
What is needed are devices that watch the interlock switches
and detect which one opened FIRST, shutting down the system.
This is what Trip Traps do. In this circuit, our harried tech
would wire a Trip Trap across each switch (figure 2).

Note how the interlock
switches are drawn conveniently close together on a diagram. The
switches themselves are often
physically placed many meters apart. This is not a problem.
Each Trip Trap is simply connected to its switch wherever it is,
no other wires need be run. Or twisted pair wires can be routed
from the interlock switches to Trip Traps located in the control
room, if that is the desired arrangement.
After the Trip Traps are wired in, all the technician must do
is start up
the process, then press the red "reset" button on each Trip
Trap. They are now ready to trap the shutdown status.
When the "hot nozzle" switch opens and shuts down the system,
its associated Trip Trap detects the shutdown and sets an
internal memory cell, trapping the shutdown status.
When the "belt stopped" switch opens, its Trip Trap does NOT set
its internal memory cell. The hot nozzle Trip Trap did that, and
each Trip Trap can sense the presence of the other Trip Traps in
the interlock chain.
When the "low pressure" switch opens, its Trip Trap also does
NOT set its internal memory cell.
When the "hot nozzle" switch re-closes, the memory cell in its
Trip Trap is NOT cleared. The only way to clear this memory cell
is to press the red "reset" button. Otherwise the shutdown status
remains trapped indefinitely.
After the shutdown, the tech would now press the green "view"
button on each Trip Trap. On three of them the "ready" lamp
would light, and on the fourth (hot nozzle) the "trapped" lamp
would light. The repair work can now be directed toward the
problem of a hot nozzle.
This is of course a very simple control circuit. A more
realistic circuit is shown in figure 3. Here the process is
started by pressing and holding the "start" pushbutton until all
the switches in the interlock chain are closed. The "start"
button is then released. The interlock chain provides the
power to keep the relay latched. If the normally closed "off"
button is pressed, or if any interlock switch opens, the relay
will drop and shut down the process. Trip Traps will work here
as well. They have sufficient impedance (50,000 ohms/volt
nominal) to ensure that the relay drops, and they are fast enough
to trap the shutdown status before the seal contact opens.

Note also that the control circuit is 24 volts AC, and the power circuit
is 240 volts AC. It is often
desirable to have a low voltage control circuit (for economy and
safety), and a higher voltage power circuit (for energy
efficiency). Trip Traps are selected for the control circuit
voltage.
The internal circuitry is powered by a lithium battery with a lifetime
rated to exceed ten years.
| Part Number | Impedance | Control Circuit Voltage |
|---|---|---|
| TT12DC | 0.6 Meg | 10 - 14 DC |
| TT24DC | 1.2 Meg | 20 - 28 DC |
| TT48DC | 2.4 Meg | 40 - 56 DC |
| TT125DC | 6 Meg | 100-140 DC |
| TT12AC | 1 Meg | 10 - 14 AC, 50/60Hz |
| TT24AC | 2 Meg | 20 - 28 AC, 50/60Hz |
| TT48AC | 4 Meg | 40 - 56 AC, 50/60Hz |
| TT120AC | 9 Meg | 105-125 AC, 50/60Hz |
| TT240AC | 18 Meg | 210-250 AC, 50/60Hz |
| TT480AC | 36 Meg | 420-500 AC, 50/60Hz |
| TT575AC | 45 Meg | 525-625 AC, 50/60Hz |